RTA Series Roof Exhausters - Belt Drive

SKU#:

RTA Series

Belt drive, heavy duty construction ideal for industrial & commercial applications.

RTA model suitable for use in clean, dry air with a maximum ambient temperature of 93º C (200º F).
RWTA models are suitable for use in moisture laden air with a maximum ambient temperature of 93º C (200º F). They feature a Teflon shaft seal, poly housing bearings and stainless steel insert.

  • TEFC, ball bearing motor is out of air stream and is accessible from the roof, maximum ambient temperature of 40º C (104º F).
  • Galvanized steel wind-band and rain-proof butterfly dampers.
  • Cast iron pillow block bearings (out of air stream), complete with external grease fittings.
  • Cast aluminum blades on 12” to 48” sizes.
  • Polypropylene blades reinforced with fiberglass on 54” to 60” sizes.
  • Heavy duty pulleys and belts out of air stream.
CFM @ STATIC PRESSURE
MODEL #RPMHPMIN CFMdBA
@
10 ft
0"1/8"1/4"1/2"3/4"1"
SINGLE PHASECFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)
BLADE DIAMETER18"RTA18T10075A15563/426005927940.45----------------------
RTA18T10075B17853/426006232030.68--29760.72------------------
RTA18T101001920126006434490.850.510.8432440.890.590.8828150.850.650.84------------
RTA18T1015022551 1/226006840431.380.371.3139011.430.441.3636531.450.501.3728631.300.601.24--------
RTA18T102002510226007245081.900.301.7643681.950.371.8041751.990.421.8434831.840.511.7128971.920.531.92----
24"RTA24T1007511803/447005850950.51----------------------
RTA24T101001295147006155820.680.910.6950940.711.030.72----------------
RTA24T1015014751 1/247006563711.000.720.9859691.040.841.0254181.050.931.03------------
RTA24T102001620247006769761.320.611.2666381.370.721.3061641.390.811.3248481.350.901.29--------
RTA24T103001890347007281782.190.442.0179102.170.551.9974862.190.632.0165792.200.752.0251652.110.791.94----
30"RTA30T10100965173005988740.881.080.8779420.941.180.93----------------
RTA30T1015010951 1/2730062100681.290.851.2392661.360.971.3082401.361.061.30------------
RTA30T1020012252730065112701.800.701.68106181.870.821.7497231.910.901.77------------
RTA30T1030013803730067127272.580.562.34121062.660.662.41113882.720.752.4694832.670.872.42--------
RTA30T1050016355730072150334.310.403.80146264.430.493.90139894.480.563.94126544.540.693.99107564.400.773.8779224.210.733.71
36"RTA36T1020091021000063166501.80--155361.83--139801.86--------------
RTA36T10300104531000066192202.72--186912.76--175502.80--144402.80----------
RTA36T10500124551000071236104.56--226794.60--217804.68--198704.75--173804.75--129804.68--
RTA36T1075014257 1/21000075271106.81--265906.87--257906.95--224107.09--222607.13--200807.13--
42"RTA42T1020077021400061199201.65--185201.72--150801.80--------------
RTA42T1030089531400065228402.60--213102.70--196202.80--149402.90----------
RTA42T10500100551400067259803.66--246693.76--232303.89--199804.01----------
RTA42T1075012057 1/21400072315206.26--307816.41--295306.54--270406.78--242306.89--202707.07--
RTA42T110001335101400075351708.49--344718.64--334108.76--312709.08--290209.32--262309.39--
48"RTA48T1030067031800063249322.770.962.50229002.111.471.94197362.871.182.59------------
RTA48T1050079051800067295384.540.703.99278004.660.844.09255044.720.944.14210294.681.074.11--------
RTA48T107509007 1/21800071333866.700.545.79322006.850.675.92303036.930.765.98258776.960.896.01--------
RTA48T11000990101800073368228.880.457.60357009.080.507.75340569.150.657.82298299.330.777.97264109.210.887.87----
54"RTA54T1050071052300068371304.26--346154.46--316804.67--------------
RTA54T107508107 1/22300071428906.20--411286.50--386606.85--332106.99--253906.87------
RTA54T11000905102300074484508.54--469118.94--446409.41--401409.73--349809.78--272209.53--
60"RTA60T107506907 1/22900068512406.45--490206.85--457607.18--357707.09----------
RTA60T11000755102900070567708.48--544408.88--514909.21--404709.43--316508.72------
CFM @ STATIC PRESSURE
MODEL #RPMHPMIN CFMdBA
@
10 ft
0"1/8"1/4"1/2"3/4"1"
THREE PHASECFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)
BLADE DIAMETER18"RTA18T30075A*15563/426005927940.45----------------------
RTA18T30075B*17853/426006232030.68--29760.72------------------
RTA18T30100*1920126006434490.850.520.8232440.890.600.8628150.850.670.82------------
RTA18T30150*22551 1/226006840431.380.381.3039011.430.451.3536531.450.501.3628631.300.611.23--------
RTA18T30200*2510226007245081.900.301.7743681.950.361.8241751.990.411.8834831.840.511.7228971.920.521.79----
24"RTA24T30075*11803/447005850950.51----------------------
RTA24T30100*1295147006155820.680.950.6750940.711.070.70----------------
RTA24T30150*14751 1/247006563711.000.740.9659691.040.861.0054181.050.951.01------------
RTA24T30200*1620247006769761.320.611.2666381.370.721.3061641.390.811.3248481.350.901.29--------
RTA24T30300*1890347007281782.190.451.9779102.170.561.9674862.190.641.9765792.200.761.9851652.110.811.91----
30"RTA30T30100*965173005988740.881.110.8579420.941.210.90----------------
RTA30T30150*10951 1/2730062100681.290.871.2292661.360.981.2882401.361.071.28------------
RTA30T30200*12252730065112701.800.691.68106181.870.811.7597231.910.891.78------------
RTA30T30300*13803730067127272.580.562.31121062.660.672.38113882.720.752.4394832.670.882.39--------
RTA30T30500*16355730072150334.310.403.81146264.430.483.91139894.480.563.96126544.540.684.01107564.400.763.8979224.210.733.72
36"RTA36T30200*91021000063166501.80--155361.83--139801.86--------------
RTA36T30300*104531000066192202.72--186912.76--175502.80--144402.80----------
RTA36T30500*124551000071236104.56--226794.60--217804.68--198704.75--173804.75--129804.68--
RTA36T30750*14257 1/21000075271106.81--265906.87--257906.95--224107.09--222607.13--200807.13--
42"RTA42T30200*77021400061199201.65--185201.72--150801.80--------------
RTA42T30300*89531400065228402.60--213102.70--196202.80--149402.90----------
RTA42T30500*100551400067259803.66--246693.76--232303.89--199804.01----------
RTA42T30750*12057 1/21400072315206.26--307816.41--295306.54--270406.78--242306.89--202707.07--
RTA42T31000*1335101400075351708.49--344718.64--334108.76--312709.08--290209.32--262309.39--
48"RTA48T30300*67031800063249322.770.972.48229002.111.501.91197362.871.192.56------------
RTA48T30500*79051800067295384.540.704.01278004.660.834.12255044.720.934.18210294.681.064.14--------
RTA48T30750*9007 1/21800071333866.700.555.74322006.850.675.88303036.930.775.95258776.960.905.97--------
RTA48T31000*990101800073368228.880.457.59357009.080.567.77340569.150.657.83298299.330.777.99264109.210.887.88----
RTA48T31500*11301518000764195813.270.3511.204110013.470.4411.393970913.590.5111.503638113.780.6411.703289913.820.7311.702957113.560.8111.50
54"RTA54T30500*71052300068371304.26--346154.46--316804.67--------------
RTA54T30750*8107 1/22300071428906.20--411286.50--386606.85--332106.99--253906.87------
RTA54T31000*905102300074484508.54--469118.94--446409.41--401409.73--349809.78--272209.53--
RTA54T31500*10251523000785552012.10--5397012.50--5211012.92--4828013.81--4431014.17--3966014.22--
60"RTA60T30750*6907 1/22900068512406.45--490206.85--457607.18--357707.09----------
RTA60T31000*755102900070567708.48--544408.88--514909.21--404709.43--316508.72------
RTA60T31500*8701529000746632012.52--6412613.12--6171013.80--5672014.43--4952014.34--3832013.51--
RTA60T32000*9552029000767309016.62--7086217.33--6888017.70--6569018.78--5927018.80--5225018.83--
For three phase motors, substitute “*” with “M” for 230/460 volt or “P” for 575 volt. If 208V is required please specify.
dBA ratings shown are measured at 0” static pressure and should be used as a guideline only.
Fan tested in accordance with AMCA Standard 210 in a figure 12A configuration.
FEP for models using a single-phase motor are determined using AMCA Standard 214-21, method 6.3 using standard air density and V-belt drive.
FEP for models using a three-phase motor are determined using AMCA Standard 214-21, method 6.4 using standard air density, V-belt drive, 4 pole TEFC motors without VFD.
Power rating does not include transmission losses.
Performance ratings do not include the effects of appurtenances.
Operation of the axial impeller in a configuration different from the published test configuration will affect performance.
                               
                              
Embedded image       
MODEL #A Dia.B Dia.C Sq.DEFG
RTA1818 3/8"24 5/8"24"2 1/2"21718
RTA2424 3/8"30 5/8"30"2 1/2"21921
RTA3030 3/8"36 5/8"36"2 1/2"22321
RTA3636 3/8"42 5/8"42"2 1/2"22527
RTA4242 3/8"48 5/8"48"2 1/2"22727
RTA4848 1/2"54 5/8"54"2 1/2"23031
RTA5454 1/2"60 5/8"60"2 1/2"23640
RTA6060 1/2"66 5/8"68"2 1/2"23640
  • Roof curb.
  • Disconnect switch.