Bucket Fan

SKU#:

BUCKET FAN

Bucket Fans are used for equalizing the floor-to-ceiling temperature. This provides a more comfortable thermal environment for occupants, while at the same time reducing energy costs. In the cold months the hot air at the roof is gently directed back down to the floor where it is needed. During the warm months in buildings that have air conditioning, Bucket Fans help push the cold air coming from the registers at the ceiling down to occupant level.

  • For use in commercial, educational, government, or industrial settings with 15’ to 30’ plus ceilings.
  • Fan casing is made of steel with polymeric coating, while impeller is made of aluminum.
  • Asynchronous motor on ball bearings.
  • Thermally protected.
  • Speed controllable.
  • Easy to install.
  • Quiet operation.
  • Hanging/Safety Cable
  • Two year warranty.
MODELRMPSONESMAX WATTSMAX AMPSAIRFLOW CFM (L/s)AIRFLOW SPEED (DEPENDING ON DISTANCE POINT -ft- FPM)VOLTS/HZ 
36101315202325303335 
BUCKET FAN 42017009.8600.51420 (198)378270220156906020____120/60 
BUCKET FAN 1055167511.3940.81055 (498)918594380234162120793820__120/60 
BUCKET FAN 1460168514.91621.381460 (689)11007567604683243002141691205919120/60 
Embedded image      
MODELMEASUREMENTSWEIGHT
(LBS)
ØDØD1HH1A
Bucket Fan 42010 3/16"13 7/16"20 3/16"15 3/16"15 3/16"6.6
Bucket Fan 105512 3/16"15 7/16"23 7/8"17 3/16"17 1/4"11
Bucket Fan 146014 3/16"17 7/16"27 5/16"20 5/16"19 3/16"12.3

HOW TO CALCULATE THE NUMBER OF BUCKET FANS YOU NEED

To enjoy the full benefit of destratification the accepted rule of thumb is to "turn the air" between one and two times an hour.

For ceiling heights 15 ft - 20 ft use the Bucket Fan 420

For ceiling heights 20 ft - 25 ft use the Bucket Fan 1055

For ceiling heights 25 ft and over use the Bucket Fan 1460

To determine how many Bucket Fans are needed use this formula:

1) L x W x H = V (Height x Width x Length = Air Volume in Building)

For Example

A building that has the following dimensions:

125 ft long, 75 ft wide, and 20 ft high.

1) 125 x 75 x 20 = 187,500 cu. ft

2) 187,500/1055/60 = 2.96 fans
V / CFM of the Bucket Fan / 60 (converts CFM to CFH) = Number of Fans

3) V / CFM / 60 = Number of Fans

Always round up to the next number. In this example 4 Bucket Fans would be needed.